• The Hub includes a FIRE IN input that can be connected to an isolated relay driven by a fire alarm system. Do not connect this input to a power supply
  • Configure the sense of the relay (normally open or normally closed) using the slide switch on the Hub (a red indicator lights up when the fire condition is indicated). A loop resistance greater than 500 kOhms will be interpreted as Open and a loop resistance less than 500 Ohms will be interpreted as Closed
  • When the FAI is used, you can configure each lock to unlock in response to the fire condition
    • For each lock, set the corresponding fire override slide switch to on. Note that you must set the power-to-lock/power-to-open switch correctly to ensure that the lock will unlock during a fire condition
  • When using the FAI feature, the installation must be tested and approved by the relevant fire authority to ensure that the behavior results in a system that is safe
  • For any power-to-open locks, do not rely on this feature for safety, as failures elsewhere in the system can result in power loss to the lock
  • This feature is not a substitute for mechanical overrides or break-glass disconnects at the exit door to allow for safe exit from the building in the event of an emergency