# AI Security Hub / Hub v1 installation

## **Getting started with AI Security Hub or Security Hub v1**

Document Number 490-0001-01

Revision 07 – 27 October 2025

{% file src="/files/Q0YB7HVQpJ6bNz0C51UZ" %}

Document Number 490-0003-01

Revision 04 – 27 October 2025

{% file src="/files/shU0QUs173xwT6WU3t1d" %}

### **What’s in the box?**

* Accessia Hub
* Hub key

### **What you’ll need**

**Equipment**

* 4 x 5mm diameter (no. 10) panhead screws and wall anchors suitable for the wall surface the Hub will be mounted on
* Tools for mounting, wiring, and knocking out and deburring cable apertures
* Appropriately sized conduit and bushes for all wiring external to the Hub
* 3mm flat-head screwdriver for wiring terminals

**Network and AC mains connection**

The Hub requires a connection to the local area network using 100BaseT Ethernet. This local area network must permit HTTPS connections to the internet. The Hub will automatically use this connection to establish a secure connection to Accessia’s cloud

### **Wiring guide**

* For the AC mains connection, see [Connecting mains and battery power](/hardware/ai-security-hub-hub-v1/mains-and-battery-power.md). Make sure that the AC mains is isolated before starting any wiring activities inside the Hub enclosure
* All other wiring in the system is safety extra low voltage (SELV) and should not be connected to any voltage greater than 30 VDC. The wiring to the DC power input and battery connection terminals is already provided using 16AWG wire. For the remaining connections, use a wire gauge in the range 14 to 24 AWG, making sure that the wire gauge is suitable for the maximum current being conducted
* The network connection must be made using Cat5 (or better) cable

### **1.** [**Mounting guide**](/hardware/ai-security-hub-hub-v1/mounting-the-hub.md)

### **2.** [**Connecting mains and battery power**](/hardware/ai-security-hub-hub-v1/mains-and-battery-power.md)

### **3. Connecting a channel**

The Hub supports up to four channels. For each channel, there are connections for:

* Up to two OSDP Readers (including RS485 signal pair and 12VDC power supply)\*
* One lock
* Two inputs with dual end-of-line (DEOL) monitoring support

Two groups of terminals are provided for the lock: wet and dry

\**2 readers per channel coming soon*

Also see: [Channel output power guide](/hardware/ai-security-hub-hub-v1/inputs-and-outputs/channel-output-power.md)

#### **3.1** [**Connecting Readers**](/hardware/ai-security-hub-hub-v1/connecting-readers.md)

#### **3.2** [**Connecting a lock**](/hardware/ai-security-hub-hub-v1/connecting-locks.md)

#### **3.3** [**Connecting an input**](/hardware/ai-security-hub-hub-v1/inputs-and-outputs/channel-inputs.md)

### **4.** [**Connecting the fire alarm interface (FAI)**](/hardware/ai-security-hub-hub-v1/inputs-and-outputs/fire-alarm-interface.md)

### **5.** [**Connecting auxiliary IO**](/hardware/ai-security-hub-hub-v1/inputs-and-outputs/auxiliary-io.md)

### **6.** [**Connecting the intruder alarm interface**](/hardware/ai-security-hub-hub-v1/inputs-and-outputs/intruder-alarm-interface.md)

### **7.** [**Learn about visual statuses**](/hardware/ai-security-hub-hub-v1/hub-visual-states.md)

## **Additional information**

### **Compatibility**

* Cloud: the Hub is only compatible with Accessia’s cloud
* Readers: the Hub is compatible with OSDP Readers

### **Programming**

Programming and configuration of the system can be done using either Accessia Installer app or the Portal

### **Software**

System software is automatically updated when necessary by Accessia’s cloud. To check the current software version, check Accessia Installer app or [Accessia Portal](http://cloud.accessia.com/)

### **Operating conditions**

AC mains input: 100 – 240VAC 50/60Hz, 3A

Operating temperature range: 32°F \~ 120°F / 0 \~ 49oC

Humidity: 20 - 90% RH non-condensing

### **Compliance**

Compliance Model CTL01A

#### **FCC**

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation\
\
Contains FCC ID: S9NBNRGM0AL

#### **UL294/UL293 Access control performance levels**

Destructive attack: Level I (Local Level III for reader RDR01A)

Line security: Level II

Endurance: Level IV

Standby Power, 60W output: Level II

Standby Power, 24W output: Level III


---

# Agent Instructions: Querying This Documentation

If you need additional information that is not directly available in this page, you can query the documentation dynamically by asking a question.

Perform an HTTP GET request on the current page URL with the `ask` query parameter:

```
GET https://docs.accessia.com/hardware/ai-security-hub-hub-v1/ai-security-hub-hub-v1-installation.md?ask=<question>
```

The question should be specific, self-contained, and written in natural language.
The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.