Auxiliary IO
The Hub includes four auxiliary inputs, AUX 1 IN, AUX 2 IN, AUX 3 IN, AUX 4 IN, and three auxiliary outputs AUX 1 OUT, AUX 2 OUT, and AUX 3 OUT. Use Accessia Installer app to configure their function
The inputs can only be connected to isolated switch (or relay) contacts. Do not connect them to a power supply. A loop resistance greater than 500 kOhms will be interpreted as Open and a loop resistance less than 500 Ohms will be interpreted as Closed
The outputs are implemented using a single-pole-double-throw relay and are electrically isolated from the rest of the system (and each other). The dry output is rated to switch a maximum of 5A and 30 VDC
Last updated
Was this helpful?